PDF of this product
Additional Product Information
pdf Eagle 120 (130 Kb)

PMI Troublemans Kit

The PMI Troubleman's Kit is a complete power quality package.
For supply side monitoring, you will receive our iVS-2SX+ By-pass Metersocket Scanner. This self-contained device will record voltage and current data for up to 12 months and features single-cycle accuracy. It installs safely between the meter-base and revenue meter. It downloads data to a Windows-compatible PC for analysis with the included cable, or the user may download data into selected Palm PDA's using the PMIScan software. For the load side, you will receive our Eagle 120 scanner.
More Information

This pocket-sized recorder plugs into a 120V receptacle to measure voltage and the current from any device plugged into the scanner. The Eagle 120 Scanner is ideal for diagnosing problems in the home, computer room, office, lab, or on the plant floor. Both of these Scanners offer optional Power, Harmonics, and Waveform Capture features! To complete the Troubleman's Kit, PMI provides you with a high-impact plastic carrying case for the scanners and accessories.

Kit includes
  • High-impact plastic carrying case
  • iVS-2SX+ metersocket scanner
  • Eagle 120 plug-in recorder
  • Communications cables
  • ProVision software package

    Specifications iVS-2SX+

    Inputs
  • AC Voltage Line-neutral 0 to 240 VAC Peak 0 to 140 VAC RMS Continuous
  • AC Current 200 Amps RMS
  • Sample rate 7,680 per channel/second
  • Recording Channels 2 voltage, 2 current

    Accuracy
  • Voltage 0.33% of full scale
  • Current 1% of full scale
  • Power 1% of full scale
  • Phase Angle 1 degree
  • Power Factor +/- 0.02
  • Displacement PF +/- 0.02

    Information Storage
  • RAM 128K (Battery Backed)
  • Flash 2MB

    Capacity
  • Summary data: Over 1 year
  • Event data 500 records
  • Significant change data 1,000 records
  • Flicker data 1,000 records

    Communications
  • Local serial cable, 4800 to 38400 baud
  • Stripcharts (4 hours to over 1 year) Voltage, Current, Power Factor, Displacement PF, Real Power, Reactive Power, Volt-Amps, Phase Angle, Harmonics.

    Controls
  • Stripchart settings 1 second to 4 hours
  • Significant change 1V to 8V, in 1V steps
  • Flicker settings User defined or standard
  • Battery voltage check: Automatic

    Power Requirements
  • Recording Load <2.5 Watts

    Environmental
  • Operating Temperature -20 to 135 F
  • Shock 60Hz to 2kHz Acceleration 25G
  • Vibration 10Hz to 60Hz . Amplitude 1.8mm

    Physical Dimensions
  • Size 4 5/8" x 6 3/4 "
  • Weight 3.6 lbs.

    Battery Ride Through
  • This battery circuit allows the "S" Series to operate with no input voltage for more than 1/2 hour. This allows it to measure down to 0 volts on all channels during power outage periods.

    Harmonics (optional)
  • Voltage measures to the 31st
  • Current measures to the 31st
  • Measures: Magnitude, Total Harmonics Distortion (THD)

    Options and Accessories
  • Power function to iVS-2SX+
  • Harmonics and Waveform to iVs2SX+
  • 8MB Memory to E120

     

  • Additional pictures

    Eagle PQ Trouble Kit

    Eagle 200 Meter Kit

    Power Flex

    Eagle 330

    Eagle Revolution

    Eagle 220

    Instruments Techno Test inc.

    Instruments Techno Test inc.
    2345, Michelin street, #100
    Laval, Qc
    H7L 5B9

    Téléphone : (450) 681-5777
    Télécopieur : (450) 681-3773

    Printed from: catalogue.techno-test.com/products/7-Power_Monitoring___Data_Logger/44-Electrical_Power_Quality/166-Troublemans_Kit-PMI_Troublemans_Kit.html