| The PMI Troubleman's Kit is a complete power quality package. |
| For supply side monitoring, you will receive our iVS-2SX+ By-pass Metersocket Scanner. This self-contained device will record voltage and current data for up to 12 months and features single-cycle accuracy. It installs safely between the meter-base and revenue meter. It downloads data to a Windows-compatible PC for analysis with the included cable, or the user may download data into selected Palm PDA's using the PMIScan software. For the load side, you will receive our Eagle 120 scanner. |
|
|
More Information
This pocket-sized recorder plugs into a 120V receptacle to measure voltage and the current from any device plugged into the scanner. The Eagle 120 Scanner is ideal for diagnosing problems in the home, computer room, office, lab, or on the plant floor. Both of these Scanners offer optional Power, Harmonics, and Waveform Capture features! To complete the Troubleman's Kit, PMI provides you with a high-impact plastic carrying case for the scanners and accessories.
Kit includes
High-impact plastic carrying case
iVS-2SX+ metersocket scanner
Eagle 120 plug-in recorder
Communications cables
ProVision software package
Specifications iVS-2SX+
Inputs
AC Voltage Line-neutral 0 to 240 VAC Peak 0 to 140 VAC RMS Continuous
AC Current 200 Amps RMS
Sample rate 7,680 per channel/second
Recording Channels 2 voltage, 2 current
Accuracy
Voltage 0.33% of full scale
Current 1% of full scale
Power 1% of full scale
Phase Angle 1 degree
Power Factor +/- 0.02
Displacement PF +/- 0.02
Information Storage
RAM 128K (Battery Backed)
Flash 2MB
Capacity
Summary data: Over 1 year
Event data 500 records
Significant change data 1,000 records
Flicker data 1,000 records
Communications
Local serial cable, 4800 to 38400 baud
Stripcharts (4 hours to over 1 year) Voltage, Current, Power Factor, Displacement PF, Real Power, Reactive Power, Volt-Amps, Phase Angle, Harmonics.
Controls
Stripchart settings 1 second to 4 hours
Significant change 1V to 8V, in 1V steps
Flicker settings User defined or standard
Battery voltage check: Automatic
Power Requirements
Recording Load <2.5 Watts
Environmental
Operating Temperature -20 to 135 F
Shock 60Hz to 2kHz Acceleration 25G
Vibration 10Hz to 60Hz . Amplitude 1.8mm
Physical Dimensions
Size 4 5/8" x 6 3/4 "
Weight 3.6 lbs.
Battery Ride Through
This battery circuit allows the "S" Series to operate with no input voltage for more than 1/2 hour. This allows it to measure down to 0 volts on all channels during power outage periods.
Harmonics (optional)
Voltage measures to the 31st
Current measures to the 31st
Measures: Magnitude, Total Harmonics Distortion (THD)
Options and Accessories
Power function to iVS-2SX+
Harmonics and Waveform to iVs2SX+
8MB Memory to E120